BIM7548 48V Isolated Bidirectional AC/DC Module 3.6kW

BIM7548 48V Isolated Bidirectional AC/DC Module 3.6kW

BIM7548 — 48V isolated bidirectional AC/DC module for telecom backup, residential storage, and mobile power systems; 2.4kW rectifier, 3.6kW inverter.

  • Isolation: High-frequency transformer, IEC 62368-1 design basis
  • Inverter output: 3600W from 39–56Vdc, 200–240Vac pure sine, 94% efficiency
  • Rectifier output: 2400W from 180–264Vac, 35–56.5Vdc, 95% efficiency
  • Battery range: 35–56Vdc; trickle charge 30–39Vdc at 8A
  • Protection: OV / UV / OC / SC / OT on both sides, 3000m altitude, pollution degree III
  • Control: Isolated CAN, parallel operation in all inverter modes, OTA firmware update

Contact: info@imaxpwr.com | +86-13760212825

Description

ImaxPWR BIM7548 48V isolated bidirectional AC/DC module, 3.6kW inverter and 2.4kW rectifier

Abstract

The BIM7548 is a 48V bidirectional AC/DC module with high-frequency transformer isolation from ImaxPWR, rated 2400W in rectifier mode and 3600W in inverter mode. It converts 180~264Vac into a regulated 35~56.5Vdc battery bus and back into 200~240Vac at 50/60Hz, reaching 95% efficiency when charging and 94% when inverting. The 338×224×83.3mm chassis carries a totem-pole bridgeless PFC stage and a full-bridge LLC converter built on third-generation power semiconductors, with CAN communication, bootloader-based firmware updates, and parallel operation in all inverter modes. It is intended for telecom backup, residential 48V storage, mobile power vehicles, and any site where the battery terminals are physically reachable by maintenance staff.

1. Where BIM7548 Sits in the 48V Module Line

The model name is readable. BIM stands for Bidirectional Isolated Module, 75 marks the 75V-class semiconductor platform used on the DC side, and 48 marks the nominal battery voltage. It replaces nothing in the existing line — it fills a gap that buyers hit constantly: every other 48V module in the 1.2–4kW band is a non-isolated design, and a non-isolated design puts the AC mains and the battery terminals on the same electrical reference.

That distinction decides which product a buyer should order. The table below compares the three modules most often quoted against each other for 48V projects.

Parameter BIM7548 BIM48-2400C BIM48-3000
Isolation High-frequency transformer Non-isolated Non-isolated
Inverter output 3600W @ 39–56V 2400W 3000–4000W
Rectifier output 2400W 2400W (charger) 3000W
Built-in MPPT No 800W No
Dimensions 338×224×83.3mm 258×161×57mm Module-dependent
Battery range 35–56Vdc 40–59.5Vdc 40–59.5Vdc
Efficiency 95% / 94% 94% 94%

Read the table as a procurement decision, not a spec sheet. If the site needs solar direct charging, order BIM48-2400C — the BIM7548 has no MPPT and adding an external charge controller costs more than the price difference. If the battery terminals sit inside a locked cabinet and only trained staff with insulated tools ever open it, a non-isolated module is cheaper and smaller. If the battery bus runs to a publicly accessible room, a vehicle, or a container that anyone can walk into, the isolated version is the only defensible choice — and that is the case this article is about.

2. What Isolation Actually Buys You

Non-isolated modules are not unsafe by definition, but their safety depends entirely on the installation staying intact. In a non-isolated AC/DC stage, the DC bus shares a reference with the AC mains. When the PFC switch fails short, or a Y-capacitor bridge develops a leakage path, mains potential appears on the DC output — which in a 48V system is the battery cable, the busbar, and every lug a technician touches.

Isolation inserts a transformer between those two domains. The BIM7548 uses a full-bridge LLC stage with a high-frequency transformer, so the 48V side is galvanically separated from the mains side. A primary-side failure can no longer energize the battery bus, and the touch current path through the installation is broken at the barrier rather than left to the installer’s earthing work.

This is the mechanism IEC 62368-1 is built around. The standard, which replaced IEC 60950-1 and IEC 60065 when both were withdrawn in December 2020, applies hazard-based safety engineering: it classifies energy sources and then requires safeguards between them, rather than prescribing constructions by product category. For converters, the practical translation is that any barrier between a hazardous mains circuit and a user-accessible circuit must be a real insulation barrier — reinforced transformer insulation, a controlled safety gap on the PCB, and an optocoupler or digital isolator carrying the feedback signal across it. A non-isolated design has no such barrier to point at; it relies on the accessible parts never becoming live.

According to the International Electrotechnical Commission, IEC 62368-1 was written to replace both IEC 60950-1 and IEC 60065, which were withdrawn in December 2020. Based on the hazard-based approach described in that standard, an isolated converter satisfies the requirement through reinforced transformer insulation, a controlled PCB safety gap, and an optocoupler or digital isolator crossing the barrier with the feedback signal.

The 48V choice itself is an industry convention rather than a product decision. According to industry guidance on telecom DC architecture, 48V sits inside the SELV band at or below 60Vdc, and for the same 240W load a 48V bus carries 5A where a 12V bus carries 20A — one sixteenth of the I²R line loss. That is why telecom standardised on it, and why storage systems keep reusing the voltage.

Why 48V is not automatically “safe voltage”. 48Vdc sits below the 60V SELV threshold that most international safety bodies use, which is why telecom has standardised on it for a century — technicians can work on a live bus with far lower shock risk, and cable losses fall dramatically against 12V for the same power (at 240W, 20A versus 5A). But SELV describes the nominal circuit. It says nothing about what happens when a mains-referenced stage fails next to it. The 60V ceiling protects you from the battery; only the isolation barrier protects you from the grid.

For a buyer, the cost question is narrower than it looks. Isolation costs board area, magnetics, and roughly 1–2 points of efficiency. On a 2.4kW module that is 24–48W of extra heat to remove, which is why the BIM7548 chassis is 338mm long against 258mm for the non-isolated 2400W unit. Set that against the alternative: a single site incident traced to a failed PFC stage, the insurance conversation that follows, and the re-certification of every installation that used the same non-isolated model. The premium is paid once; the exposure is carried for the life of the site.

3. Operating Modes and Power Flow

BIM7548 power topology from AC grid through totem-pole PFC and LLC transformer to 48V battery
Power path of the BIM7548: the LLC transformer and the red barrier separate the mains domain from the SELV battery bus.

The module runs two directions through the same magnetics, switched by the onboard DSP. There is no mechanical transfer switch and no external contactor.

Rectifier mode (AC to DC). The AC input accepts 180~264Vac at 45~65Hz. A totem-pole bridgeless PFC front end holds power factor at 0.98 and THDi at 7% at rated load, then the LLC stage delivers a regulated 35~56.5Vdc output capped at 2400W. Charging efficiency is 95% at rated input into a 48V battery. A separate trickle-charge path covers 30~39Vdc at 8A for deeply discharged packs, so a flat battery recovers without tripping protection. The current regulation accuracy is 2% across the 20–100% load band, which matters when the BMS is the thing deciding when to stop.

Inverter mode (DC to AC). The battery side accepts 35~56Vdc and produces 200~240Vac sine wave at 50 or 60Hz, manually switchable, factory-set to 230V/50Hz. Output power is not flat across the battery range: 3600W from 39~56V, 3300W from 38~39V, and 3000W from 35~38V. That derating curve is worth reading before sizing — a 3.6kW load on a pack that sags to 37V under load will be limited to 3.3kW, not 3.6kW.

Four stages of over-power protection sit behind that: 3900–4800W locks after 10s, 4800–6000W after 3s, 6100–7200W after 200ms, all requiring manual restart; a separate 35–39V branch protects at 3300–4500W and 4500–5400W. Instant short-circuit protection auto-restarts, but a short held for more than 5 seconds latches and needs a manual restart. Plan the enclosure so the restart button is reachable without opening a live compartment.

All inverter modes support parallel operation, so capacity scales by adding modules rather than replacing one. CAN carries power, current, voltage, frequency, protection status, and charge/discharge state; the same bus accepts bootloader-based firmware updates, which means a fleet can be updated remotely instead of by site visits.

4. Technical Specifications

4.1 Inverter Output (DC to AC, 3600W)

Parameter Min Rated Max Remarks
DC input voltage (Vdc) 35 48 56 35–39V derates to 3000W
AC output voltage (Vac) 200 230 / 220 240 Pure sine, default 230V, manually switchable
AC output frequency (Hz) 49 / 59 50 / 60 51 / 61 Manually switchable, default 50Hz
Output power (W) — 3600 @ 39–56V — 3300W @ 38–39V, 3000W @ 35–38V
Peak efficiency — 94% DC/AC conversion
THD — ≤3% — 48Vdc input, rated resistive load
Over-power protection 1 3900±50W to 4800±50W Locks after 10s, manual restart
Over-power protection 2 4800±50W to 6000±50W Locks after 3s, manual restart
Over-power protection 3 6100±50W to 7200±50W Locks after 200ms, manual restart
Short circuit protection Instant trip, auto-restart Latches if short exceeds 5s

4.2 Rectifier Charging (AC to DC, 2400W)

Parameter Min Rated Max Remarks
AC input voltage (Vac) 180 230 264 Under-voltage trip 170V, over-voltage 268–275V
AC input frequency (Hz) 45 50 / 60 65 Wide range suits weak grids
Input current (A) — 13.2 — At 2600W maximum input power
Power factor — 0.98 — 50–100% output load, rated input
THDi — 7% — Rated input, full load
Inrush current (A) — 20 — Cold start
Output voltage range (Vdc) 35 48 56.5 Constant power, 2400W max
Trickle charge (Vdc / A) 30 39 8A Recovers deeply discharged packs
Charging efficiency — 95% — Rated input, 48V output
Current regulation accuracy — 2% — 20–100% of rated output current
Voltage / current ripple — 2% / 10% — 20MHz bandwidth, 0.01s/div
Start-up response — 10s — From monitoring command to output live

4.3 Mechanical, Environmental, and Protection

Dimensions (W×D×H) 338 × 224 × 83.3 mm
Cooling Fan-forced air cooling, low-noise fan supplied by the host system
Operating temperature −10°C to +40°C
Storage temperature −40°C to +70°C
Humidity 10–90% RH, no condensation (operating and storage)
Operating altitude Up to 3000 m
Pollution degree III
Over-temperature protection Ambient 55°C, low-voltage side 120°C, high-voltage side 100°C
Battery-side protection Over-voltage 57.5V (recover 57V), under-voltage 33.5V sustained 2s (recover 34.5V)
No-load consumption 25W
Safety & EMC EN 55022 Class B (6dB margin), IEC 62368-1, RoHS
PCB finish Conformal coating on both sides
Control interface CAN (isolated), AC_EN discharge enable (active high, 3.3V/0V), 9V/300mA auxiliary supply
Wiring UL3135 AWG#12, 200°C rated, ≥2.0 kgf terminal pull strength

5. Where the Isolation Ends Up Mattering

Isolated versus non-isolated 48V AC/DC module comparison for battery terminal safety
The trade-off in one picture: the isolated unit costs size and a few points of efficiency, and buys a fault path that stops at the barrier.

Specification tables do not tell a buyer where a module belongs. These four deployment patterns do.

Telecom base stations and edge cabinets. A −48V DC plant normally keeps its battery bus inside a locked cabinet, which is the argument for saving money with a non-isolated rectifier. The counter-argument is maintenance: cell sites get visited by riggers, cleaning contractors, and diesel top-up crews who are not power engineers. Every one of them opens the cabinet door. An isolated rectifier means the battery terminals stay at SELV potential no matter what the AC side does, and the site does not depend on a technician remembering to check the earth bond.

Residential and small commercial 48V storage. Homeowners touch their equipment. A 48V lithium pack with an inverter bolted to the same wall is reached by anyone who opens the utility closet, and in many markets the installation is inspected by an electrician who has never seen the module before. High-frequency isolation keeps the battery side separated from mains, which simplifies the enclosure design: no need to treat the battery compartment as a hazardous-voltage zone.

Mobile power and vehicle-mounted systems. A moving chassis flexes harnesses and vibrates connectors. The failure mode that matters is a damaged AC cable contacting the DC loom. With isolation, that fault stays on the mains side of the barrier; without it, the vehicle chassis and the battery negative can become live together.

Weak-grid and high-altitude sites. The 180–264Vac input window rides through the voltage swings common on rural feeders, and the 3000m altitude rating covers most of the highland deployments in Latin America and Central Asia. Pollution degree III and two-sided conformal coating are the practical answer to dust and humidity in coastal or desert installations — not a marketing line, but the difference between a three-year life and a five-year one.

6. Frequently Asked Questions

Q1: Is the isolation premium worth it compared with a non-isolated module?

It depends on who can reach the battery terminals. If the DC bus lives in a locked cabinet opened only by trained staff, a non-isolated module is smaller and cheaper and there is no technical reason to refuse it. If the terminals are reachable by cleaners, tenants, drivers, or contractors, the isolated version removes a failure mode you cannot engineer out of a non-isolated design. Frame the decision as an insurance cost, not a specification upgrade.

Q2: Why is the inverter rated 3600W when the rectifier is only 2400W?

Because the two directions are sized for different loads. Inverter mode drives motor starts, air conditioners, and inductive loads where short-term peak matters; rectifier mode charges a battery whose BMS sets the acceptable current. The asymmetry is deliberate — it lets a 48V pack supply a 3.6kW load while still charging at a rate most 100Ah packs can accept. Note the output derates to 3300W at 38–39V and 3000W at 35–38V, so size the battery so it does not sag into those bands under load.

Q3: Does it work with both lead-acid and lithium batteries?

Yes, within the 35–56.5V window. A 48V lead-acid string (24 cells) sits comfortably in range, and 16S LiFePO4 (nominally 51.2V) fits with headroom at both ends. Charging voltage and current are set over CAN from the host controller or BMS, so the module follows the profile it is given rather than imposing one. If the BMS cannot speak CAN, the module can run on its internal defaults — confirm the profile before commissioning.

Q4: Can modules be paralleled for more capacity?

All inverter modes support parallel operation, which is how a 3.6kW module becomes a 7.2kW or 10.8kW system without changing platform. Paralleling requires the CAN bus to be wired between units and a host controller to handle load sharing; it is not a plug-and-play cable. Plan the CAN topology and addressing at design stage — retrofitting a parallel bus into a finished cabinet is the expensive version.

Q5: What certifications and documents come with the module?

The design complies with EN 55022 Class B with 6dB margin, IEC 62368-1, and RoHS. A user manual covering specifications, terminal definitions, and CAN protocol is available, along with structural drawings for enclosure design. For projects requiring a specific national mark, request the compliance documents at quotation stage — certification scope differs by market and the document set should be confirmed before the order rather than after.

Related Products

  • BIM48-2400C — the same 48V / 2400W class with an 800W built-in MPPT and 20ms UPS bypass, for sites that need solar direct charging.
  • BIM48-3000 — 3–4kW non-isolated variant when the battery bus stays inside a locked enclosure.
  • BIM48-1500 and BIM48-1800 — smaller 48V modules for cabinet-level power where 2.4kW is more than the load requires.
  • BIM300120 — 15kW-class bidirectional AC/DC module for C&I storage cabinets, when the project outgrows the 48V band.
  • Full product center — the complete ImaxPWR conversion lineup, from 1.2kW modules to megawatt PCS.

About the Author

Ethan Li is an energy storage systems engineer at ImaxPWR Power Co., Ltd., with years of experience in PCS, DC/DC converters, BESS, and microgrid design. He has participated in multiple domestic and international energy storage projects in solution design and technical support. Reviewed by Ethan Li.

About ImaxPWR

ImaxPWR Power Co., Ltd. is a National High-Tech Enterprise founded in 2019 and headquartered in Shenzhen, China. As a source manufacturer, we cover bidirectional converters, DC/DC, energy management, and energy storage cabinet integration, providing design, delivery, and O&M services. Our R&D team comes from State Grid, XJ Group, Emerson, Kehua Tech, and other listed power companies, and we hold multiple invention patents and software copyrights.

Request the full datasheet or a customized configuration for this product — contact us directly.
Email: info@imaxpwr.com | Tel / WhatsApp: +86-13760212825 | imax-pwr.com

© 2026 ImaxPWR Power Co., Ltd. All rights reserved. Specifications in this article are taken from the BIM7548 User Manual V2.0. Standards referenced: IEC 62368-1 (hazard-based safety engineering for audio/video, IT and communication equipment) and EN 55022 Class B (conducted and radiated emission limits for IT equipment).

Get In Touch​

We will reply you in 24 hours​
Talk to an Engineer
Join 100+ Industry Leaders – Get Your Custom Solution

We use cookies to personalize and enhance your browsing experience on our website. By clicking “Agree”, you agree to the use of cookies. You can read our Cookie Policy for more information.

Read
Chat with engineer
Request a Quote Engineer reply within 24h