8 kW Bidirectional Isolated DC/DC Module · BIDC40023 / BIDC75016
8 kW Bidirectional Isolated DC/DC Module
Two bus-voltage variants, one battery interface: 30–160 Vdc battery side, 160 A continuous charge and discharge, 96.5% peak conversion efficiency, high-frequency isolation between battery and busbar.
By Ethan Li · Reviewed by Ethan Li · ImaxPWR engineering
96.5% peak efficiency
160 A continuous
<100 ms response

What this module does
A battery bank and a DC bus rarely sit at the same voltage. The BIDC40023 and BIDC75016 sit between them: a high-frequency isolated DC/DC converter that moves 8 kW in either direction, between a 30–160 Vdc battery and a 400 V or 750 V DC busbar.
The battery side is where the difference shows. A 30–160 Vdc window covers 48 V, 60 V, 72 V and 96 V battery banks on the same module, and the converter holds 160 A continuously in both charge and discharge — one current envelope for both operating modes, so cable and fuse sizing does not split into two calculations. Switching between charge, discharge and automatic operation is handled internally, with a conversion response under 100 ms.
Isolation is high-frequency, between battery and busbar. That matters on DC microgrids and vehicle-to-vehicle setups where the battery side floats at a different potential than the bus, and where a ground fault on one side should not propagate to the other.
Two variants — pick by bus voltage, not by power
Both models deliver 8 kW. The difference is the DC bus window they are built for.
According to the module’s published ratings, the higher-voltage variant carries the same 8 kW in a narrower bus current — 16 A instead of 23 A — because the bus voltage is roughly 1.9 times higher.
Design points that matter in the field
Isolation sits where the risk is
The high-frequency transformer separates battery from busbar, so a fault on the bus side does not ride through to the battery bank. Grounding schemes stay independent on both sides.
160 A in both directions
Charge and discharge share the same current envelope, so a battery cable or a fuse is sized once rather than twice.
96.5% leaves less heat to move
At 8 kW, 96.5% against a 94% design is roughly 200 W of extra dissipation inside a 220 × 84 × 400 mm chassis. Air cooling stays adequate to 60 °C.
Parallel to the power you need
Modules parallel for higher system power, so a design can start at 8 kW and grow without changing converter platform or control interface.
RS485 and CAN on board
Both interfaces are native, so the module talks to a BMS, an EMS or an upper-level controller without an external protocol gateway.
Rack-shaped, front maintained
220 × 84 × 400 mm and under 6 kg — a module that slides into a standard subrack and comes out without dismantling the cabinet.
Where the module fits
Three applications keep appearing in enquiries for this power class, and all three share one shape: a low-voltage battery on one side, a higher DC bus on the other, energy travelling both ways.
DC microgrids
A 48 V or 96 V battery buffering a 400 V DC distribution rail. The 30–160 Vdc window means one module type covers several battery builds, and isolation keeps the battery side independent of the bus grounding.
Vehicle-to-vehicle transfer
Moving charge between two battery systems of different voltages. The 160 A continuous rating sets the transfer speed, and the under-100 ms reversal keeps the direction change from showing up as a bus disturbance.
Power-supply aging and burn-in
Test racks that cycle a battery or a power supply for hours need a converter that holds current in both directions without a second unit for the return path. Parallel operation scales the rack without changing the module.
Based on the published specification, nominal power is reached at a battery input of at least 50 Vdc, so a deeply discharged pack at the bottom of the 30 V window will not deliver the full 8 kW until voltage recovers.
Integration notes
Thermal. The module is air-cooled and derates linearly above 40 °C, reaching its limit at 60 °C. Size the enclosure airflow against the site’s real maximum ambient rather than the 60 °C ceiling.
Paralleling. Multiple modules operate in parallel for higher system power. Because charge and discharge share one current envelope, the parallel count can be set from the total transfer current alone.
Control. RS485 and CAN are both native. The control layer sees one converter with a direction command, not a charger plus a separate discharge path.
Mechanical. 220 × 84 × 400 mm at under 6 kg fits a standard subrack slot, so spares can be swapped from the front of the cabinet.
Commissioning. Because the ratio condition is a hard limit rather than a derating curve, the bus voltage setpoint belongs in the commissioning checklist. Set the bus, then walk the battery up through its range and confirm the module stays in conversion across the whole window — not only at the nominal operating point.
Technical specifications
| Parameter | BIDC40023 | BIDC75016 |
|---|---|---|
| Busbar side | ||
| Bus voltage range | 250–550 Vdc | 450–1000 Vdc |
| Rated voltage | 400 Vdc | 750 Vdc |
| DC bus current (max) | 23 A | 16 A |
| Rated power | 8 kW (bus input ≥ 380 Vdc) | 8 kW (bus input ≥ 720 Vdc) |
| Bidirectional conversion condition | Vbus / Vbat > 14 / 6 | Vbus / Vbat > 28 / 6 |
| Battery side | ||
| Battery voltage | 30–160 Vdc | |
| Rated voltage | 50 Vdc | |
| Battery current (max) | 160 A | |
| Rated power | 8 kW (battery input ≥ 50 Vdc) | |
| General | ||
| Peak conversion efficiency | 96.5% | |
| Charge / discharge response | <100 ms | |
| Current ripple | ≤ ±3% | |
| Voltage ripple | ≤ ±1% | |
| Dimensions (W × H × D) | 220 × 84 × 400 mm | |
| Weight | <6 kg | |
| IP rating | IP20 | |
| Noise | <60 dB | |
| Operating temperature | −40 to 60 °C (linear power reduction above 40 °C) | |
| Cooling | Air-cooled | |
| Communication | RS485, CAN | |
| Protection | Over-current, over-voltage, over-temperature, short-circuit, DC reverse connection | |
Worked examples at three battery voltages
The ratio test is quick to run by hand. The table below takes three common battery voltages at the top of their operating range and applies the 14 : 6 threshold of BIDC40023 against a 400 V nominal bus.
| Battery voltage (top of range) | Required bus for 14 : 6 | 400 V bus verdict |
|---|---|---|
| 96 Vdc | 224 Vdc | Works — bus is well above the threshold |
| 128 Vdc | 299 Vdc | Works — comfortable margin |
| 160 Vdc | 374 Vdc | Works, but only above 374 V — a 400 V nominal bus is tight at the low end of grid tolerance |
That last row is where projects go wrong. A 400 V nominal bus that sags to 360 V during a grid disturbance leaves a 160 V battery below the ratio, and the module stops instead of limiting power. If the battery can reach 160 V and the bus is not tightly regulated, the 750 V variant buys the margin.
Choosing between the 400 V and 750 V variant
The selection is not a preference. Each variant has a minimum bus-to-battery voltage ratio, and below that ratio the module faults out rather than operating at reduced power.
For BIDC40023 the ratio is 14 : 6. A battery at 160 V needs a bus of at least 160 × 14 ÷ 6 = 374 V to run. For BIDC75016 the ratio is 28 : 6 — the same 160 V battery needs at least 160 × 28 ÷ 6 = 747 V.
That single number drives the choice. A 48 V battery on a 400 V bus gives a ratio near 8 : 1, comfortably above 14 : 6, so BIDC40023 fits. The same 48 V battery on a 750 V bus reaches roughly 15 : 1 and needs the higher ratio only if the battery is pushed toward 160 V — check the top of the battery range, not the nominal point, because the ratio degrades as battery voltage rises.
Frequently asked questions
Can one module cover both 48 V and 96 V battery banks?
Yes. The battery side accepts 30–160 Vdc, so 48 V, 60 V, 72 V and 96 V banks all fall inside the window. Rated power is specified at a battery input of at least 50 Vdc.
Does the 400 V variant work on a 550 V bus?
The bus window is 250–550 Vdc with a 400 V rating, so 550 V is inside the range. What changes is current headroom: keep bus current within 23 A and re-check the bus-to-battery ratio.
What happens above 40 °C ambient?
Output power reduces linearly above 40 °C up to the 60 °C limit. Plan the thermal design around the site’s real maximum ambient, not the 60 °C headline.
Is it a charger or a converter?
Both directions are native. The module supports charge, discharge and automatic switching between the two, with a conversion response under 100 ms, so it can sit on a bus that both absorbs and supplies energy.
Where is it normally used?
DC microgrids, vehicle-to-vehicle energy transfer, and power-supply aging or burn-in racks — three cases that share a low-voltage battery, a higher DC bus and a need to move energy in both directions.
Related products
- IMDC100100 5 kW bidirectional isolated DC/DC module — the smaller frame of the same isolation concept, for 5 kW battery-side conversion.
- IMDC300120 15 kW bidirectional DC/DC converter — next step up in power, 40–300 Vdc battery side.
- BIDC1000250 250 kW bidirectional DC/DC converter — for plant-level DC coupling rather than module-level integration.
- All bidirectional DC/DC and MPPT converters — the full range from 2.4 kW to 250 kW.
Still comparing power classes? The product selector filters the whole catalogue by type, power and form factor.
Sizing a 30–160 Vdc battery onto a DC bus?
Send the battery voltage window, bus voltage and required power. We will confirm the variant and the ratio margin before you order.
info@imaxpwr.com | +86-13760212825
© ImaxPWR · IMAX Power Technology Co., Ltd. · www.imaxpwr.com (CN) · imax-pwr.com (EN)