Description
Excellent Safety Performance: “6-Layer” Heavy-Duty Safety Protection Ensures Zero Accidents
Rigorous Testing & Certification
We conduct multiple thermal runaway and safety tests to guarantee product reliability. These stringent evaluations ensure that our systems meet the highest safety standards in the industry.
Seamless Switching Capability
Our system switches between grid-connected and off-grid modes seamlessly, ensuring uninterrupted power supply across various applications. This feature is crucial for commercial and industrial storage, micro-grids, and regional energy storage.
Enhanced Grid Regulation
By improving the flexibility of power distribution stations, our solution boosts grid regulation capabilities. This leads to more efficient energy management and utilization.
Significant Economic Benefits: Enjoy Up to 20 Years of Returns with a Single Investment
High-Efficiency Integrated Design
Our optically integrated storage systems minimize CAPEX and OPEX, offering substantial cost savings over the long term. This design philosophy ensures maximum return on investment.
Here is the information presented in a table format:
Category | Parameter | Value(s) |
---|---|---|
Model | Imax30-100WP/50-114WP | |
DC Side | Specifications | 30kW/100kWh; 50kW/114kWh |
Battery Type | LFP/280Ah | |
System Nominal Capacity | 100.352kWh; 114.688kWh | |
Grouping Method | 112S1P; 128S1P | |
Battery Voltage Range | 302.4V – 408.8V; 332.8V – 467.2V | |
PV Parameters | Maximum Power | 38.4kW; 76kW |
Maximum Voltage | 850V | |
Starting Voltage | 250V | |
MPPT Voltage Range | 200V – 830V | |
Maximum Input Current | 32A + 32A (two-circuit); 32A+32A+32A+32A (four-circuit) | |
AC Side (Grid-connected) | Output Power | 30kVA (when battery voltage is below 320V, 28kVA); 50kVA |
Maximum Output Current | 50A; 80A | |
Rated Voltage Range | -20% – 15% | |
Frequency Range | 50Hz/47Hz – 52Hz; 60Hz/57Hz – 62Hz | |
Harmonic | < 3% (above 30% load) | |
AC Side (Off-grid) | Rated Power | 30kVA; 50kVA |
Rated Current | 43.5A; 80A | |
Rated Voltage | 400V/230V | |
Output Voltage Harmonic | < 2% (resistive load) | |
Frequency Range | 50Hz/60Hz | |
Output Overload (Current) | 1.25/10s, 1.5/100ms | |
System Parameters | Operation Mode | Grid-connected and off-grid operation |
System Efficiency | >85% (AC side, @25±2°C, 0.33P) | |
Power Factor | -1 – 1 (adjustable) | |
Cooling Method | Air-cooling | |
Allowable Working Temperature Range | Charging: 0 – 55°C; Discharging: -20 – 55°C | |
System Cycle Times | >6000 times (@25±2°C, 0.5P, EOL≥80%) | |
Altitude | ≤2000m (above 2000m, derating required) | |
Weight | 1700kg; 1900kg | |
External Communication | Ethernet, wireless 4G | |
Protection Level | IP54 | |
Anti-corrosion Level | C3 | |
External Electrical Interface | 3L+N+PE | |
Cabinet Size (WDH) | 1220mm1200mm2000mm |