Description
The IM100-10K series high-frequency switching rectifier module is an AC-DC module with adjustable AC voltage input and DC voltage output. The module adopts DSP digital control, resonant soft switching, active PFC technology, and is protected by multiple patents.
Function Description:
- High Efficiency:
Reduces energy consumption and loss, complies with energy-saving and emission-reduction requirements, and saves electricity costs for customers. - High Power Density:
Saves customer space and reduces system costs. - DSP Digital Control:
Fewer components, higher environmental stability, higher reliability, and more convenient expansion. - Low Input Harmonics:
Reduces pollution to the power grid and improves grid adaptability. - Wide Input Voltage Range, Wide Output Voltage Range:
Suitable for the vast majority of different input and output voltage scenarios. - Wide Operating Temperature Range:
The wide operating temperature range meets most harsh working environments. - Hot Swapping:
Suitable for convenient use and reduces maintenance costs. - Comprehensive Fault Self-Detection and Warning:
Rich fault detection for easy customer maintenance.
Product Specification Parameters:
Specification Parameters | IM48-9K | IM100-10K | LM150-10K | LM120-10K |
---|---|---|---|---|
DC Output | ||||
Rated Output Power | 9kW | 10kW | ||
Rated Output Current | 150A | 100A | 75A | 92A |
Output Voltage Range | 20VDC ~ 60VDC | 30VDC ~ 100VDC | 50VDC ~ 150VDC | 40VDC-120VDC |
Current-Limiting Adjustable Range | 10% – 110% steplessly adjustable | |||
Peak-to-Peak Noise | ≤1% | |||
Telephone Harmonic Noise | No requirement | |||
Voltage Stabilization Accuracy | ≤±0.5% | |||
Current Stabilization Accuracy | ≤±1% | |||
Average Current | ≤±5% | |||
Efficiency | ≥95% | |||
AC Input | ||||
Rated Input Voltage | Three-phase 380Vac/480Vac | |||
Input Voltage Range | 323Vac ~ 520Vac (full load), 323Vac ~ 260Vac (linear reduction to half load) | |||
Input Current | <20A | |||
Frequency | 45Hz ~ 65Hz | |||
Power Factor (PF) | ≥0.99 | |||
Total Harmonic Distortion (THD) of Current | ≤5% | |||
Input Protection | Fuse; Lightning protection circuit | |||
Working Environment Conditions | ||||
Working Environment Temperature | -40°C ~ 50°C normal operation; 50°C ~ 75°C reduced output; | |||
Storage Temperature | -40°C ~ 75°C | |||
Relative Humidity | 0 ~ 95% | |||
Altitude | Maximum operating altitude 4000m, no derating below 2300m, above 2300m, derate 1% for every 100m increase |
Product Safety and Reliability
|
|
MTBF
|
>120000 hours
|
Insulation Strength
|
Input to chassis can withstand 50Hz effective value 2500VAC or equivalent 3535VDC withstand voltage for 1 minute; Input to output can withstand 50Hz effective value 3000VAC or equivalent 4242VDC withstand voltage for 1 minute
|
Dimensions and Weight
|
|
Dimensions
|
130 (width) × 84 (height) × 396 (depth)
|
Module Net Weight
|
7Kg
|
Communication and Alarm
|
|
Communication Interface
|
CAN
|
Maximum Parallel Quantity
|
60 units
|
Output Positive and Negative Insurance Protection
|
|
Alarms and status are monitored on – site through the CAN communication port, and indicated by three panel LEDs
|