High-efficiency energy storage, smart energy. Explore the innovation Product Center and open up a new future for green energy

100V10KW low-voltage rectifier module voltage stabilizing power supply

100V10KW low-voltage rectifier module voltage stabilizing power supply

Output Voltage Range 20VDC ~ 60VDC
Current-Limiting Adjustable Range 10% – 110% steplessly adjustable
Rated Input Voltage Three-phase 380Vac/480Vac
Input Voltage Range 323Vac ~ 520Vac (full load), 323Vac ~ 260Vac (linear reduction to half load)
Working Environment Temperature -40°C ~ 50°C normal operation; 50°C ~ 75°C reduced output;
Storage Temperature -40°C ~ 75°C
MTBF >120000 hours
Module Net Weight 7Kg
Dimensions 130 (width) × 84 (height) × 396 (depth)


Description

The IM100-10K series high-frequency switching rectifier module is an AC-DC module with adjustable AC voltage input and DC voltage output. The module adopts DSP digital control, resonant soft switching, active PFC technology, and is protected by multiple patents.

Function Description:

  • High Efficiency:
    Reduces energy consumption and loss, complies with energy-saving and emission-reduction requirements, and saves electricity costs for customers.
  • High Power Density:
    Saves customer space and reduces system costs.
  • DSP Digital Control:
    Fewer components, higher environmental stability, higher reliability, and more convenient expansion.
  • Low Input Harmonics:
    Reduces pollution to the power grid and improves grid adaptability.
  • Wide Input Voltage Range, Wide Output Voltage Range:
    Suitable for the vast majority of different input and output voltage scenarios.
  • Wide Operating Temperature Range:
    The wide operating temperature range meets most harsh working environments.
  • Hot Swapping:
    Suitable for convenient use and reduces maintenance costs.
  • Comprehensive Fault Self-Detection and Warning:
    Rich fault detection for easy customer maintenance.

 

Product Specification Parameters:

Specification Parameters IM48-9K IM100-10K LM150-10K LM120-10K
DC Output
Rated Output Power 9kW 10kW
Rated Output Current 150A 100A 75A 92A
Output Voltage Range 20VDC ~ 60VDC 30VDC ~ 100VDC 50VDC ~ 150VDC 40VDC-120VDC
Current-Limiting Adjustable Range 10% – 110% steplessly adjustable
Peak-to-Peak Noise ≤1%
Telephone Harmonic Noise No requirement
Voltage Stabilization Accuracy ≤±0.5%
Current Stabilization Accuracy ≤±1%
Average Current ≤±5%
Efficiency ≥95%
AC Input
Rated Input Voltage Three-phase 380Vac/480Vac
Input Voltage Range 323Vac ~ 520Vac (full load), 323Vac ~ 260Vac (linear reduction to half load)
Input Current <20A
Frequency 45Hz ~ 65Hz
Power Factor (PF) ≥0.99
Total Harmonic Distortion (THD) of Current ≤5%
Input Protection Fuse; Lightning protection circuit
Working Environment Conditions
Working Environment Temperature -40°C ~ 50°C normal operation; 50°C ~ 75°C reduced output;
Storage Temperature -40°C ~ 75°C
Relative Humidity 0 ~ 95%
Altitude Maximum operating altitude 4000m, no derating below 2300m, above 2300m, derate 1% for every 100m increase
Product Safety and Reliability
MTBF
>120000 hours
Insulation Strength
Input to chassis can withstand 50Hz effective value 2500VAC or equivalent 3535VDC withstand voltage for 1 minute; Input to output can withstand 50Hz effective value 3000VAC or equivalent 4242VDC withstand voltage for 1 minute
Dimensions and Weight
Dimensions
130 (width) × 84 (height) × 396 (depth)
Module Net Weight
7Kg
Communication and Alarm
Communication Interface
CAN
Maximum Parallel Quantity
60 units
Output Positive and Negative Insurance Protection
Alarms and status are monitored on – site through the CAN communication port, and indicated by three panel LEDs

Get In Touch​

We will reply you in 24 hours​

Get In Touch

We will reply you in 24 hours,

We respect your confidentiality and all information are protected.